The Tekron NTS and TCG product ranges have the ability to synchronise to an IRIG-B input signal. The IRIG-B signal should include either a CTQ (Continuous Time Quality) quality flag if using the C37.118 standard or a CF (Control Functions) flag if using an earlier IEEE standard.
Tekron clocks support IRIG-B004 to IRIG-B007 formats, please refer to the link for more information about the contents of each format.
How to determine what IRIG-B format is being outputted.
Please note:
- IRIG-B 003 does not have control functions and therefore cannot be used for IRIG-B input.
- NTS100 does not support IRIG-B input.